24 VDC
85-132/176-264 Vac
115/230 Vac, Auto select
85-132/176-264 Vac
5 / 2 A typ.
47 - 63 Hz
> 88% typ. (32.7 W)
typ. < 40 A
78347215321
Units Fulfill EN61000-3-2
24 Vdc (22.5 - 28.5 Vdc adj.)
< 50 mVpp
Fold Forward (Current rises, voltage drops to maintain constant power during overload up to max peak current)
> 20 ms @ full load
10 A (240 W)
< ±2% overall (combination Line, load, time and temperature related changes)
< 33 Vdc
Single or Parallel use is selectable via Front Panel Switch
5 year limited warranty
12.00
-10C to +60C
EN61000-6-3, -4; Class B EN55011, EN55022 Radiated and Conducted including Annex A. EN61000-3-2
Protected against continuous short-circuit, overload, open-circuit. Protection Class 1 (IEC536), degree of protection IP20 (IEC 529) Safe low voltage: SELV (acc. EN60950)
-25C to +85C
The relative humidity is < 90% RH, noncondensing; IEC 68-2-2, 68-2-3.
Green LED and DC OK signal (N.O. Solid State Contact rated 200 mA / 60 Vdc)
1.00
Two connectors per output, connector size range: 16-10 AWG (1.5 - 6 mm2) for solid conductors
Simple snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional screw mounting set SDN-PMBRK2 required).
IP20-rated screw terminals, connector size range: 16-10 AWG (1.5-6 mm2 ) for solid conductors. 16-12 AWG (0.5-4 mm2)
Fully enclosed metal housing with fine ventilation grid to keep out small parts.
> 600,000 hours
5
5
4
Not available at this time.